Frigomatic R134a Charging Guidelines

General

The following is intended for the use of a boat operator with average mechanical skills. It will describe what symptoms to look for in a correctly charged Frigomatic system, & how to adjust the charge if an undercharged or overcharged condition exists. Working with refrigerants involves potentially dangerous pressures and temperatures and precautions must be taken to avoid injury. Eye & skin protection must be worn when working on refrigeration systems. Do not open the high-pressure service valve on your Frigomatic system, or connect anything to it. If you are unsure about your ability to safely accomplish any of the following procedures or if you cannot positively identify the low and/or high-pressure service valves, consult a marine refrigeration specialist. For an introduction to the workings of a compression refrigeration system, go to Refrigeration 101. Before deciding which condition exists in your system, please read all of the following thoroughly. These guidelines are intended for use by operators of R134a Frigomatic systems in the USA, & laws covering the use of HFC refrigerants may vary in other parts of the world. In all cases it is the duty of the person performing the service to verify that he/she is not violating any laws or regulations by following these guidelines. All items needed for correcting the charge are readily available in auto or hardware stores. No refrigerant gauges are necessary for these adjustments, their use is not recommended except for major repairs & for evacuating the system, & no reference will be made to them in this guide.

Section 1; Symptoms of correct & incorrect charge

Correctly charged system

The Frigomatic systems are capillary tube systems, & require a precise refrigerant charge to work at maximum efficiency. Too much or too little refrigerant will result in a systems that will have some cooling effect, but will not be working to it’s full potential. In a Frigomatic system, the temperature of the evaporator is directly related to the amount of refrigerant in the system. There should be enough refrigerant in the system so that the last of the liquid is evaporating back to a vapor at the very end of the evaporator, & just as it enters the suction tube back to the compressor. After running for a time, there should be a slight coating of frost all over the surface of the evaporator, & there should be no condensation or frost on the exposed section of copper tube back to the compressor, & no condensation on the compressor itself. If the system has been installed correctly, the short length of insulation supplied with the system should be positioned on the copper tube starting where it exits the refrigerated box. No other insulation is required, and any extra that has been installed will only cause the system to run at less than maximum efficiency & may conceal symptoms of an overcharge. This short length of insulation is installed to prevent any condensation that may occur as the cold tube leaves the refrigerated box & is exposed to hot, humid air. In a properly charged system, there should be a “tinny, gurgling” sound from the evaporator.

Slightly undercharged system

If there is too little refrigerant in the system, it will have all evaporated back to a vapor long before it reaches the end of the evaporator. Some of the surface will have a coating of frost, but from the point on from where all the refrigerant has turned to vapor, the surface will just be cold & sweating. By following the channels in the evaporator, it can be determined the path that the refrigerant follows, & the end of the capillary tube can be easily identified. This is where the liquid refrigerant is fed into the evaporator, & so will be where the frosting begins. The evaporator will probably sound the same as a properly charged system.

Seriously undercharged system

If the system is seriously undercharged, the refrigerant may exist in the system only as a vapor, & so there will be no frosting on the evaporator. Just a slight sweating & cold to the touch. In this condition there will probably be a constant hissing sound from the evaporator. This is important in identifying if the system is undercharged or overcharged.

Slightly overcharged system

Too much refrigerant in the system will result in liquid still evaporating back to a gas past the end of the evaporator & inside the tubing going back to the compressor. This means that there is still some of the refrigeration process going on inside the tubing, & there will be a build-up of frost or ice on the exposed section. If additional insulation has been added, it may be concealing this symptom & should be removed. The evaporator may appear & sound normal, but will be at a higher temperature than desired, resulting in longer than expected run times.

Seriously overcharged system

If so much refrigerant exits in the system that it raises the temperature of the evaporator above 32 deg F, the surface will only be sweating & cold to the touch, resembling an undercharged condition. But the copper lines leading back to the compressor, & maybe even the compressor itself will be also be cold & sweating, & there will probably be a sound similar to a mountain stream coming from the evaporator. This is a potentially damaging condition as liquid can reach the compressor where it can damage the valves, & refrigeration compressors are designed to compress gas only.

Section 2; Adding refrigerant

Tools and parts required

No special tools are required, but the following items will need to be purchased from an auto parts or hardware store.

Connecting to the Frigomatic system

First, you need to confirm that undercharged condition exists, & not a seriously overcharged one, as described in Section 1. If the system is seriously undercharged due to a leak, the problem will need to be rectified & the system evacuated with a vacuum pump before re-charging. Screw the Valve Assembly on to the can of refrigerant & then screw the Adapter on to the Valve Assembly. Locate the end of the Charging Hose that has a valve stem depressor, & screw the opposite end onto the Adapter. Locate the suction side service valve & remove the valve cap. The suction side service valve is normally situated on a stub that is attached directly to the top of the compressor. If there are two service valves, make sure that you attach the hose to the suction valve and not the discharge valve. Do not remove the valve cap from the discharge side service valve or connect anything to it. If you cannot positively identify the suction side service valve, consult a marine refrigeration specialist. Prepare the can of R134a for charging. This is usually achieved by screwing in the handle on the top of the Valve Assembly to pierce the can, but follow specific instructions supplied with your equipment. With the system idle & having not run for 10 –15 minutes, allow a small amount of refrigerant to be discharged from the Charging Hose to purge air from the hose, & then screw the end of the hose onto the suction side service valve.

Adding refrigerant

Run the system for a while & then add a small amount of refrigerant. This is usually achieved by backing off the handle on the top of the Valve Assembly, but check your specific instructions as some equipment may differ. Keep the can of R134a in an upright position while adding refrigerant so that no liquid is allowed to enter the system. Add the refrigerant in small amounts (say 5 seconds) & then let the system “settle down” for approx. 10 minutes. You should see the frosted area on the evaporator increase after adding some refrigerant, & then the process may be repeated if necessary until the symptoms of a correctly charged system are met (see Section 1). Make sure that the valve on the can of R134a is firmly closed after adding refrigerant. As the refrigerant is added, the can of R134a may become very cold & even have frost forming on the outside. When the charge in the system is correct according to the conditions described in Section 1, remove the Charging Hose from the suction side service valve while the system is running. Replace the valve cap firmly.

Section 3; Removing refrigerant

Locating the suction side service valve

It is very important that you correctly identify the suction and discharge (if fitted) service valves. The suction side service valve normally will be on a stub of tubing that is connected directly to the top of the compressor. If you are unable to positively identify the suction side service valve, consult a marine refrigeration specialist.

Releasing refrigerant

Run the system long enough for the symptoms of an overcharge to exist & then remove the valve cap from the suction side service valve. With the system running, & wearing gloves & eye & skin protection, cover the top of the valve with a rag or paper towel & hold it there with one hand. Slide the end of a screwdriver or similar tool under the rag or towel with your free hand, & depress the valve core for a short time (say 5 seconds). This should allow some refrigerant gas to escape & maybe some refrigerant liquid. If liquid is released it will immediately evaporate at very low temperatures, & so all precautions must be taken to avoid contact between liquid refrigerant & skin or eyes. There will probably be some oil that is released with the refrigerant and this is normal. After releasing some refrigerant, let the system “settle down” for approx. 15 minutes & then visually check the system. On a slightly overcharged system you should see the frost line on the tubing move back towards the evaporator or disappear completely. Repeat the process as necessary until the system shows the symptoms of a correct charge as described in Section 1. On a seriously overcharged system it may take repeated releases before the symptoms of a slight overcharge appear. When the charge has been adjusted correctly replace the valve cap firmly.